VCES-DDC-IOM-1C
5
being used then you must not provide any jumpers to ter-
minals 304, 305, 306, 307 or 308.
The remote unit control multi-state variable is used to en-
able the unit through a Bacnet interface. Set MV12 to:
2 for unoccupied mode.
4 for occupied recirculation mode (optional).
6 for unoccupied recirculation mode (optional).
10 for ventilation mode.
The VHC unit can be configured to control building tem-
perature a variety of ways. Adjust #153 – Zone Configura-
tion to change temperature control to discharge air, room
air or return air control. Default settings from factory allow
the unit to be controlled by discharge air temperature.
Adjust the following setpoint:
#153 – Zone Configuration
Limits: NO, RM, RET
Factory set: NO
BACnet variable: MV11 function – Zone configura-
tion allows the unit to be used for zone heating and
cooling.
NO: No zone control (discharge only)
RM: Room air zone control (BacStat II)
RET: Return air zone control (RA temp sensor)
Discharge Air Temperature Control
(MV11 = NO)
This type of control is used when the VHC is required to
maintain a discharge temperature only. The BacStat will
not provide room control in this mode. An optional ther-
mostat may be used to provide additional heating or cool-
ing when connected to the heating override or cooling
override terminals on the FW terminal strip (see Override
Contact Control (Optional)).
Adjust the following setpoints:
#107 – Cooling Setpoint
Limits: 50–80°F [10–27°C]
Factory set: 60°F
BACnet variable: AV10 function – The cooling set-
point is the temperature that the reheat will heat the
supply air up to (summer mode only).
#115 – Coil Leaving Setpoint
Limits: 40–65°F [4–18°C]
Factory set: 55°F
BACnet variable: AV143 function – The coil leav-
ing setpoint is the temperature that the cooling coil
will cool the coil leaving air temperature down to
during discharge air temperature control (summer
mode only).
#111 – Heating Setpoint
Limits: 50–105°F [10–40°C]
Factory set: 80°F
BACnet variable: AV20
Function: The heating setpoint is the temperature
that the post heat will heat the supply air up to dur-
ing discharge air temperature control (winter mode
only).
Room Air Temperature Control (MV11 = RM)
The BacStat must be mounted in the room for this type of
control.
This type of control is used when you want to maintain a
room temperature. The VHC will heat/cool based on the
BacStat temperature. An optional thermostat can be used
to provide additional heating or cooling when connected
to the heating override or cooling override terminals on
the FW terminal strip (see Override Contact Control (Op-
tional)).
Adjust the following setpoints:
#147 – Summer Zone Setpoint
Limits: 60–80°F [15–25°C]
Factory set: 70°F
BACnet variable: AV84 function – The summer zone
setpoint is the room or return air setpoint for sum-
mer mode.
#150 – Winter Zone Setpoint
Limits: 60–80°F [15–25°C]
Factory set: 70°F
BACnet variable: AV87
Function: The winter zone setpoint is the room or re-
turn air setpoint for winter mode.
Return Air Temperature Control
(MV11 = RET)
This type of control is used when you want to maintain
a return temperature. This application is typical for VHC
units providing air to several rooms. The VHC will heat/
cool based on the return air temperature. An optional
thermostat can be used to provide additional heating or
cooling when connected to the heating override or cooling
override terminals on the FW terminal strip (see Override
Contact Control (Optional)).