Venmar 1200 cfm Manual do Utilizador Página 24

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 28
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 23
Page 24
Options
Dirty Filter Sensor
The dirty filter sensor option will monitor the
pressure across the filters and will close contacts
when dirt restricts the airflow to the setpoint. The
connections at the external terminal interface
will close and can be used to control a remote
light or alarm to signal dirty filters.
The sensor has the following features:
Pressure setpoint is factory set.
Polyester film diaphragm responds to pressure changes as
low as 2.5mm WC.
Equipped with male quick connect terminals.
Connection ports accept standard .2" [5mm] rubber or plastic
tubing.
In the vertical plane the mounting orientation is free.
Specifications:
Electrical Rating:
1.5 Amp. 220/240 VAC (resistive)
Ambient Temperature Range:
14°F to 158°F [-10°C to +70°C]
Ambient Humidity Range:
5 - 90% RH at 104°F [40°C] non-condensing
Switch Action: SPDT
Terminals: 1/4" [6mm] quick connect
Pipe Connection: 1/4" [6mm] outside diameter
Mounting: Within 10% of vertical
Material:
Diaphragm - polyester film
Switch mounting plate - zinc-coated steel
Housing - PET
Maximum Sustained Pressure: 60mm WC
External Finish - Paint
The following options for external finish are available for
certain Venmar CES heat recovery ventilator units:
galvanized metal, non painted.
baked-on, polyester, grey or white pre-painted surface on
galvanized metal.
corrosion resistant package offers powder coated surface
on the exterior and interior of the galvanized steel cabinet to
prevent corrosion.
Not all external finish options are available for all units. See
the Physical Data - Nomenclature Options chart on page 3 for
specific unit information.
Dampers
Damper options are available in pressure open/gravity
closed, power open/power closed or power open/spring closed.
Backdraft Damper
Standard backdraft dampers have the following features:
All aluminum construction provides a long, rust-free
operational life.
Blades are extruded aluminum profiles and secure-
ly linked via a large diameter aluminum linkage rod.
Silicone seals are provided as standard to ensure
sealing longevity and remain flexible down to
-40°F/°C.
Self-lubricating celcon bearings ensure a maintenance-free
and long-cycle life.
Backdraft dampers are designed for operation in tempera-
tures ranging between -40°F and 212°F [-40°C and 100°C].
Air leakage through a 24" x 24" [610 x 610mm] backdraft
damper does not exceed 20 cfm/sq.ft. against 1" w.g.
[0.25kpa] differential static pressure at standard air.
Non Insulated Damper
Non-insulated dampers have the following features:
Extruded aluminum blades and frame contribute to a long,
rust-free operational life.
Blade gaskets are extruded EPDM elastomer.
Frame seals are extruded TPE thermoplastic.
Seals provide outstanding dynamic fatigue
resistance that ensures sealing longevity.
Seals provide excellent resistance to weath-
ering, compression set and heat.
Bearings are comprised of a celcon inner
bearing fixed to a 7/16" [11mm] aluminum
hexagon blade pin rotating within a polycar-
bonate outer bearing inserted in the frame.
Dual bearing system is self-sealing, self-lubricating and
non-absorbent.
Dampers are designed for operation in temperatures
ranging between -40°F and 212°F [-40°C and 100°C].
Air leakage through a 48" x 48" [1220 x 1220mm] damper
does not exceed 10.3 cfm/sq.ft. against 4" w.g. [1kpa]
differential static pressure at standard air.
Pressure drop of a fully open 48" x 48" [1220 x 1220mm]
damper does not exceed 0.02" w.g. [0.005kpa] at 1000 fpm
[5.08m/s].
Insulated Damper
Insulated dampers have the following features:
Extruded aluminum blades and frame contribute to a long,
rust-free operational life.
Thermally insulated blades are constructed
using an aluminum shell, injected with
polyurethane foam.
Insulated blades have an insulating factor of
R-2.29 and a temperature index of 55.
Blade gaskets are extruded EPDM elastomer.
Frame seals are extruded TPE thermoplastic.
Non-metallic blade and side seals minimize
thermal bridging across blade surfaces.
Seals provide outstanding dynamic fatigue resistance that
ensures sealing longevity.
Bearings are comprised of a celcon inner bearing fixed to a
7/16" [11mm] aluminum hexagon blade pin rotating within a
polycarbonate outer bearing inserted in the frame.
Dual bearing system is self-sealing, self-lubricating and
non-absorbent.
Dampers are designed for operation in temperatures ranging
between -40°F and 212°F [-40°C and 100°C].
Air leakage through a 48" x 48" [1220 x 1220mm] damper
does not exceed 4.12 cfm/sq.ft. against 4" w.g. [1kpa] differ-
ential static pressure at standard air.
Pressure drop of a fully open 48" x 48" [1220 x 1220mm] damper
does not exceed 0.03" w.g. [0.0075kpa] at 1000 fpm [5.08m/s].